1.0 INTRODUCTION
UL S2203
CyberCat 50 Operation Manual
1-23
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
Exhibit 1-21: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Graphic
Annunciator
(256 LED)
Address Y
2
- 32
LED Number
Y
3 - 256
LED Function
Y
No Function Assigned
/
Device Activation / Device
Trouble / Device Activation or
Trouble / Device Pre-Alarm /
Device Activation or Pre-
Alarm / Zone State Activation
/ Switch 1 Feedback / Switch
2 Feedback / Switch 3
Feedback / Switch 4
Feedback / Panel Silenced /
Panel Drill / Panel Walk Test /
Sounder / Network Device
Activation / Network Device
Trouble / Network Device
Activation or Trouble /
Network Device Pre-Alarm /
Network Device Activation or
Pre-Alarm
Device (selection)
Y
(PNL) 1 – 128: (Loop) 1 – 4,
(Add) 1 – 254
1
Activation State
Y
Alarm
/ Pre-alarm / Process /
Trouble / Supervisory / Zone
Disable / Pre-Discharge /
Release
2
Zone Assignments
Y
1 - 254
2
Network Device (selection)
Y
(PNL) 1 – 128: (Loop) 1 – 4,
(Add) 1 – 254
3
LED Illumination Pattern
Active State
Y
Off / Continuous /
Slow Blink
/ Fast Blink
Inactive State
Y
Off
/ Continuous / Slow Blink
/ Fast Blink
Silenced State
Y
Off /
Continuous
/ Slow Blink
/ Fast Blink
Acknowledged State
Y
Off /
Continuous
/ Slow Blink
/ Fast Blink
Piezo Y
Enabled
/ Disabled
Notes:
1.
Configuration options become available if LED Function is set to ‘Device’.
2.
Configuration options become available if LED Function is set to ‘Zone State Activation’.
3.
Configuration options become available if LED Function is set to ‘Network Device’.