1.0 INTRODUCTION
UL S2203
CyberCat 50 Operation Manual
1-3
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
1.5.4
EMERGENCY COMMUNICATION SYSTEM
The AAP1 (P/N 10-2831) and AAP3 (P/N 10-2832) audio adjunct panels are compact, self-contained, and
cost-effective digital audio adjunct panels that can be interfaced with the CyberCat 50 panel (firmware version
6.00 or higher) to provide the following ECS functions: In-building Fire Emergency Voice/Alarm
Communications (EVACS) and In-building Mass Notification (MNS).
The AAP1 and AAP3 provide a simple user interface that allows responding personnel to quickly and
accurately convey live or prerecorded fire or mass notification commands to building occupants. The AAP1
and AAP3 panels do not have fire-fighter’s phone capabilities.
Each audio adjunct panel includes a single, 50 watt, audio amplifier equipped with four Class B or A speaker
circuits standard. The amplifier is configurable for either 25 or 70 Vrms output. The amplifier is capable of
communicating information to a single audio zone (single channel) in order to facilitate an appropriate
response and action to a fire or emergency event. Two additional 50 watt amplifiers can be added to the
AAP3 to expand its output capabilities to serve up to three audio zones or to increase the single audio zone
output to 150 watts. Each amplifier is capable of storing up to sixteen (16) individual, custom audio messages
(maximum 30 seconds in length) and tones in a digital format on the board’s internal memory for playback.
Refer to Section 3.1.8 for further details.