5.0 SYSTEM DIAGNOSTICS
5-4
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
5.5.1.1
DEVICE TYPE, LOCATION AND LED DIAGNOSTICS
The Device Type Diagnostic screen allows you to compare the type of addressable device held in the panel’s
configuration at a specific address to the type of device present/found on the signaling line circuit (SLC).
From the Device Diagnostic Menu, press the F1 button to display the Device Loc & LED Diagnostic screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L O O P : N A D R : 0 0 1 - 0 2 0
D
B
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
C
C O N F I G U R E D
D E V
T Y P E
D
P R E S E N T
D E V I C E
T Y P E
Exhibit 5-3: Device Type Diagnostic Screen
•
Row A (LOOP) - Allows you to select the loop number, represented by ‘
N
’. Use the
◄►
buttons
to position the cursor under the field; then press the
+/-
buttons to change to desired loop
(
CyberCat 50 has only 1 loop
).
•
Row A (ADR) - Allows you to select the address range to display in groups of 20. Use the
◄►
buttons to position the cursor under the first digits (001 in this case); then press the
+/-
buttons to
increment/decrement the group selection
•
Row A (D) - Allows you to toggle between D or L:
D - Displays the device types in Rows C and D.
L – Allows you to light the LED for the device (red/green flash). To light the device LED, use
the
◄►
buttons to position the cursor under the field; then use the +/- buttons to set field to
L. Then use the
◄►
buttons to position the cursor under the desired address on Row D.
Toggle the LED status by pressing the +/- button at the specific address location.
•
Row B - These numbers act as placeholders for the range of addresses selected in Row A.
•
Row C - Displays the type of device programmed in the configuration for the specific address
displayed:
P = Photo
H = Heat
F = FAAST
D = DUCT
M = Monitor, 4”
- = Unknown
Y = Relay
m = Mini Monitor
U = Photo/Heat
I = Ion
T = Pull Station
2 = Dual Monitor
C = Control
Z = Conventional Zone
•
Row D - Displays the type of device present/found connected on the addressable loop at the
specific address displayed. Same device types as shown in Row C description above.
L
Note:
The panel loads this screen upon reset and does not provide live updates as loop
changes are made. Therefore, the panel must be reset in order to update this screen if wiring
or SLC status is modified.