5.0 SYSTEM DIAGNOSTICS
5-2
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
5.4
REMOVING OR REPLACING FIELD DEVICES
If it is determined that a field device is defective and needs to be replaced:
1. First, use the system programming software to download the current system configuration from the
panel.
2. Disconnect the system batteries then remove AC power.
I
Caution:
Removing or replacing field devices when power is applied could damage the
equipment.
3. Disconnect field wiring from field device(s).
4. Remove and replace the defective field device(s) following the installation instructions supplied with
the device(s).
I
Caution:
The CyberCat 50 field devices contain static sensitive components. Handle the
electronics by the edges only and avoid touching the integrated components.
Keep all electronics in the protective static bags it was shipped in until time for
installation. Always ground yourself with a proper wrist strap before handling the
module(s). If the installer is properly grounded at all times, damage due to static
discharge will not occur. If the module requires repair or return to Fike, it must be
shipped in an anti-static bag.
5. Reapply power to the system by reconnecting AC power then connecting system batteries.
6. Reconnect all field wiring.
7. Resend configuration to device(s), if applicable.
8. Functionally test the operation of the system to verify proper operation.