5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 50 Operation Manual
5-7
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
5.5.3 VALUE
2
DIAGNOSTIC
The Value 2 Diagnostic screen allows you to view the panel’s signaling line circuit (SLC) monitoring data
(displayed in an analog-to-digital reference data). From the Diagnostic Menu 1, press the F3 button to
display the Loop Monitoring Data screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
C 1 + 2 2 5
C 1 - 0 0 3
B
C
D
Exhibit 5-6: Value 2 Diagnostic Screen
•
Row A (C1+) = Loop 1 ++ supervision trouble < 100
•
Row A (C1-) = Loop 1 – supervision trouble >100
5.5.4 LED
TEST
From the Diagnostic Menu 1, press the F4 button to briefly illuminate all LEDs on the CyberCat 50 display for
approximately 10 seconds. The message “SENDING LED TEST” appears briefly to indicate the command
has been sent. In addition, an LED test command is sent to all devices connected to the panel’s peripheral
bus causing them to briefly illuminate all device LEDs. During the LED test, all characters on the LCD display
will go solid, as shown below.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
B
C
D
Exhibit 5-7: LED Test Screen
5.5.5
CRC (CYCLIC REDUNDANCY COUNT)
The CRC screen allows you to view the current firmware version of the CyberCat 50 controllers main
processor, main loop processor (loops 1 and 2), and auxiliary loop processor (loops 3 and 4). From the
Diagnostic Menu 1, press the F5 button to view the Cyclic Redundancy Count screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
P R O G R A M
C R C : A A 3 6
B
M A I N
P I C V E R : 5 . 0 0
C
A U X L
P I C
V E R : - . - -
D
P R E S S E N T E R T O C A L C
Exhibit 5-8: CRC Diagnostic Screen
•
Row A - Displays the main system processor CRC value (V5.00/AA36).
•
Row B - Displays the main loop (SLC 1 & 2) processor firmware version.
•
Row C - Displays the auxiliary loop (SLC 3 & 4) processor firmware version.
•
Row D - Press ENTER button to calc. The newly calculated CRC will be displayed on Row A.