5.0 SYSTEM DIAGNOSTICS
5-20
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
2. Digital Paging Card Values
¾
A### - A-D value (0 – 255) for contact monitor supervision (Short range = 180 – 255, Open range
= 0 – 50, Normal range = 51 – 179)
¾
B### - A-D value (0 – 255) for local/master fire-phone trouble supervision when not used for
paging or party line (Short range = 155 – 255, Open range = 0 – 78, Normal range = 79 – 154)
¾
C### - A-D value (0 – 255) for local/master fire-phone off hook supervision (Off hook range = 176
– 255, Open range = 0 – 100, On hook range = 101 – 175)
¾
D### - Audio bus troubleshooting (Increments periodically if the amplifier does not receive any
valid packets on the audio bus. Once the counter reaches max value of 255, it stays at 255 until
the fault clears. Once the amp starts receiving valid packets, the counter is decremented
periodically.
¾
E### - A-D value (0 – 255) for fire-phone riser trouble supervision when not used for paging or
party line (Short range = 193 – 255, Open range = 0 – 7, Normal range = 8 – 192)
¾
E### - A-D value (0 – 255) for fire-phone riser trouble supervision when used for paging or party
line (Short range = 193 - 255, Open range = 0 – 89, Normal range = 90 – 192)
¾
F## through J## – NOT USED
¾
K## - Audio bus master or slave (Slave = 0, Master = 1)
¾
L## - Contact monitor (Not active = 0, Active = 1)
¾
M## - Paging control card switch priority level (0 = highest, 8 = lowest)
¾
N## - Contact monitor priority level (0 = highest, 8 = lowest)
¾
O# - Microphone trouble
No trouble = 0
Not connected = 1 (check pin #3 on P8)
Wiring trouble 1 = 2 (check pin #2 & 8 on P8)
Wiring trouble 2 = 4 (check pin #1 & 7 on P8)
Wiring trouble 3 = 6 (check pin #1, 2, 7 & 8 on P8)
¾
P# - Fire-phone Class-A configuration (Disabled = 0, Enabled = 1)
¾
Q# - Contact monitor latching/non-latching configuration (Non-latching = 0, Latching = 1)
¾
R# - Contact monitor normally open/closed configuration (Normally open = 0, Normally closed = 1)
3. Remote Paging Card Values
¾
A##, B##, C## – NOT USED
¾
D### - Audio bus troubleshooting (Increments periodically if the amplifier does not receive any
valid packets on the audio bus. Once the counter reaches max value of 255, it stays at 255 until
the fault clears. Once the amp starts receiving valid packets, the counter is decremented
periodically.
¾
E## through J## – NOT USED
¾
K## - Audio bus master or slave (Slave = 0, Master = 1)
¾
L## - NOT USED
¾
M## - Paging control card switch priority level (0 = highest, 8 = lowest)
¾
N## - NOT USED
¾
O# - Microphone trouble
No trouble = 0
Not connected = 1 (check pin #3 on P8)
Wiring trouble 1 = 2 (check pin #2 & 8 on P8)
Wiring trouble 2 = 4 (check pin #1 & 7 on P8)
Wiring trouble 3 = 6 (check pin #1, 2, 7 & 8 on P8)
¾
P# through R# - NOT USED