3.0 SYSTEM OPERATION
3-6
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
3.3.2 NORMAL
STATE
The system operates in Normal State when no alarm or troubles exists. In the Normal State, the control panel
does the following:
1. Green AC POWER LED illuminates.
2. Supervises loop devices (requests device status every 8 seconds). If device fails to report, panel will
indicate DEVICE MISSING trouble within 1 minute. Likewise, if a new device is present on the
system and not in the panel configuration, a DEVICE NOT IN CONFIG trouble will be reported.
3. LED on SLC devices will blink every 5 seconds.
4. SLC devices communicate their status directly to other devices (peer-to-peer).
5. Supervises panel NAC and auxiliary power circuits.
6. Supervises AC/DC power.
7. Supervises devices connected to peripheral bus.
8. Displays a system normal message as follows:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C Y B E R
C A T
5 0 P T
v x . x x
B F I K E
C O R P O R A T I O N
C 0 8 : 0 0 : 0 0 A
0 8 / 0 1 / 2 0 0 7
D A L : 0 0 0
S U : 0 0 0
T R : 0 0 0
Exhibit 3-3: System Normal Display
•
Row A – Displays a standard system message including panel name and firmware operating version.
•
Row B – Displays a 20 character custom message that can be changed to suit your project
requirements.
•
Row C – Displays the current system time and date.
•
Row D – Displays the number of Alarm (AL), Supervisory (SU), and Trouble (TR) events present on
the system.