1.0 INTRODUCTION
UL S2203
CyberCat 50 Operation Manual
1-15
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
Exhibit 1-13: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Mini Monitor
Module)
Loop Number of Device
Y
1
1
Address of Device
Y
1
– 50
Custom Message
Y
60 character user defined
(1-001 MINI MANALRM
Loop 1 - Address 001)
Custom Message
Y
Default /
User Defined
Zone Assignments
Y
1
– 254
2
Alarm Verification
Y
Time: 0 – 60 seconds
Y
Enabled
/ Disabled
Input Function Type
Y
No Input Function
/
ManAlarm / Detection/
Waterflow /Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / PAS
Inhibit / Reset / Silence /
Acknowledge / Drill / Zone
Disable / Fan Restart /
Smoke Control Confirmation /
Manual Alarm Stage 2 / AHU
Fire Dept Key / Voice Alert /
Voice Evacuation / Voice
Play Message ID / MNS Play
Message ID
Y
Verify Time: 0 – 255 seconds
3
Y
Latching
/ Non-Latching
4
Y
Normally Open
/ Normally
Closed
5
Y
No Short Detection
/ Short
Detection
Voice/MNS Priority
Y
1
- 255
6,
7
Msg 1 ID
Y
0
- 16
8
Msg 2 ID
Y
0
- 16
8
MNS Timeout
Y
0
- 250
9
Defaults
(Pull Station
Module)
Loop Number of Device
Y
1
1
Address of Device
Y
1
– 50
Custom Message
Y
60 character user defined
(1-001 PULL STATION
Loop 1 - Address 001)
Custom Message
Y
Default/
User Defined
Zone Assignments
Y
1
– 254
2
Input Function
Y
No Input Function
/ Manual
Alarm
Notes:
1.
CyberCat 50 has only one (1) addressable loop with a maximum of 50 devices.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
If monitor module function type is set to Detection, an alarm verification time can be set.
4.
Either = PA1, PA2, Supervisory, Trouble, Process, PAS Inhibit; Non-Latch = Reset, Silence, Acknowledge, Zone Disable, Fan
Restart; Latching = ManAlarm, Detection, Waterflow, Drill.
5.
NO Contacts = Detection, Manual Alarm, Reset, Supervisory; NO/NC Contacts = Process, Waterflow, PA1, PA2, Trouble, Drill,
Silence, Acknowledge, Zone Disable, PAS Inhibit, Fan Restart.
6.
Priority field becomes available only when Input Function is set to a Voice or MNS function.
7.
Priority setting cannot be set the same as the panel priority settings for Alarm, Test Alarm, Supervisory, and Process.
8.
Message ID field becomes available only when Input Function is set to Voice or MNS Play Message ID.
9.
MNS Timeout field becomes available only when input Function is set to MNS Play Message ID.