6.0 SYSTEM MAINTENANCE
6-12
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
6.4.2.4
DEVICE CONFIGURATION READ
This menu provides a means to read the configuration of all addressable devices connected to the panel.
From the Maintenance Menu 2, press the F4 button to access the screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E A D
A L L
D E V I C E S
B
O
N L O O P S : 1 2 3 4
C
P R E S S E N T E R
T O
S T A R T
D
D E V I C E S
T O
R E A D : N N N N
Exhibit 6-20: Configuration Read Screen
•
Row B - Use the
◄►
arrow buttons to move the cursor under the loop number; then use the +/-
buttons to select or deselect the loop for reading. Press ENTER to start the “Reading” process.
•
Row D – ‘NNNN’ shows the total number of devices the panel will read. This number will
decrement each time a device has been read.
6.4.2.5 FAAST
This menu provides a means to read the diagnostic condition of the FAAST detector connected to the panel,
as well as isolate and disable the detector. The isolate condition allows the unit to continue to operate and
annunciate alarms without affecting outputs. The disable condition turns off the detector fan and prevents the
device from detecting alarms. The disable condition will be maintained through panel reset. From the
Maintenance Menu 2, press the F5 button to access the screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L O O P : 1
A D R : 0 0 1 - 0 2 0
B
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
C
- - - - - - - - - - - - - - - - - - - -
D
F 1 - R D F 2 - I S O L
F 3 - D I S
Exhibit 6-21: FAAST Screen
•
Row A - Use the
◄►
arrow buttons to move the cursor under the loop number and address range
fields; then use the +/- buttons to select the loop and address range.
•
Row B – These numbers act as placeholders for the range of addresses selected in Row A.
•
Row C – Shows the status letter for the FAAST detector that aligns with the address number on
Row B. Only FAAST detectors are displayed. Non FAAST detectors are shown as “-“.
−
F
= indicates that the detector is not isolated or disabled.
−
I
= indicates that the detector is isolated.
−
D
= indicates that the detector is disabled.
•
Row D – Displays the actions that are available for the FAAST detector selected in Row C.
−
F1-RD
= forces a read of the diagnostic condition of the FAAST detector.
−
F2-ISOL
= sends the isolate (if the letter is
F
in row C) or de-isolate (if the letter is
I
in row C) command to the FAAST detector.
−
F3-DIS
= sends the disable (if the letter is
F
in row C) or enable (if the letter is
D
in
row C) command to the FAAST detector.