5.0 SYSTEM DIAGNOSTICS
5-22
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
5.8.3.1
VOICE ZONES STATUS
The Voice Zones Status screen allows you to view the enabled/disabled status of individual voice zones.
From the Voice Zones screen, press the F1 button to view the Voice Zones Status screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A L E R T :
D
Z O N E : 0 0 1
B
E V A C :
D
A L L
P A G E : E
C
F P A G E : D
M N S
P A G E : D
D
F M S G :
D
M N S
M S G :
D
Exhibit 5-28: Voice Zones Status Screen
•
Row A (Zone:) - Allows you to select the zone that will be displayed. Use the
◄►
arrow keys to
position the cursor under the appropriate field; then use the +/- buttons to increment or decrement
the field value.
•
Rows A-D – Displays the
E
nabled/
D
isabled status of the selected zone’s output messages for
each of the following states:
“ALERT”
“EVACUATE”
“FIRE PAGE”
(includes Page with Record and Repeat)
“FIRE MESSAGE”
(per zone)
“ALL PAGE”
(Page to Alert, Page to EVAC, Page All, and Page All with Record and Repeat)
“MNS PAGE”
(per zone)
“MNS MESSAGE”
(per zone)
5.8.4
PERIPHERAL FIRMWARE VERSION
The Peripheral Firmware Version screen allows you to view the firmware version of the selected peripheral
bus device. From the Diagnostic Menu 4 screen, press the F4 button to view the Firmware Version screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
P E R I P H E R A L
A D D R :
0 2
B
T Y P E :
D I G I T A L P A G I N G
C
F I R M W A R E
V E R S I O N
D
X X . X X
Exhibit 5-29: Firmware Version Screen
•
Row A - Allows you to select the address of the peripheral device (1 – 32) that will be displayed in
Rows C and D. Use the +/- buttons to increment or decrement the peripheral address.
•
Row B – Displays the type of peripheral device currently configured at the peripheral address
selected in Row A.
Available Peripheral Devices:
Rem Disp 14Key
Print+Gateway (MIM)
Switch 20-Zone
Digital Paging
256 LED Graphic
Gateway Only (MIM)
Annunc 20-Zone
Relay Control
Zone Graphic
Ethernet Port
Computer
Class A Module
Print Serial (MIM)
Rem Disp 10Key
Amplifier
Remote MIC
Bosch DACT
Rem Disp 2 Key
Fire-Phone Int
Print Parallel (MIM)
Smoke Control
6Z Voice EVAC
•
Row C – Displays “FIRMWARE VERSION” unless the selected device is an amplifier card; then
this row will display “DS PIC” and its firmware version.
•
Row D – Displays “FIRMWARE VERSION” unless the selected device is an amplifier card; then
this row will display “NAC PIC” and its firmware version.