5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 50 Operation Manual
5-9
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
5.6.2 VESDA 1 DIAGNOSTICS
The VESDA 1 Diagnostics screen allows you to view the current obscuration reading and activation set points
from the selected VESDA unit. From Diagnostic Menu 2 screen, press the F2 button to view the VESDA 1
Diagnostic screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
V E S D A
Z O N E
N U M :
0 0 1 >
B
C U R R E N T : 0 . 0 0 0 0 % / F T
C
A L : - . - - - -
A C : - . - - - -
D
F 1 : - . - - - -
F 2 : - . - - - -
Exhibit 5-11: VESDA 1 Diagnostics Screen
•
Row A - Allows you to select the VESDA zone number to view. Use the
◄►
arrow buttons to
position the cursor in ones, tens, or hundreds field; then press the +/– buttons to change the
value at cursor. Arrow (< >) moves back and forth to indicate communication with VESDA unit.
•
Row B - Displays current obscuration being seen at the VESDA detector selected in Row A. This
updates upon each press of ENTER button (noted in %/ft value)
•
Row C (AL) - Displays the current Alert setting (in obscuration %/ft.) for the detector selected in
Row A.
•
Row C (AC) - Displays the current Action setting (in obscuration %/ft.) for the detector selected in
Row A.
•
Row D (F1) - Displays the current Fire 1 setting (in obscuration %/ft.) for the detector selected in
Row A.
•
Row D (F2) – Displays the current Fire 2 setting (in obscuration %/ft.) for the detector selected in
Row A.