5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 50 Operation Manual
5-25
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
5.9.3 PLAY MESSAGE ID STATUS
The Play Message ID Status screen allows you to view the voice message numbers being transmitted by the
panel to the amplifiers. From the Diagnostic Menu 5 screen, press the F3 button to view the Play Message
ID Status screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A C T I V E
M E S S A G E
I D
B
Z O N E : 0 0 0
P : n n n
S : x x x
C
S I L E N C E : O F F
C I T Y : x
D
M N S
R E S E T : n n n D I S A B L E
Exhibit 5-33: Play Message ID Status Screen
•
Row B (Zone) – Allows you to select the zone number (1 – 253) that will be displayed in Row B.
Use the +/- buttons to increment or decrement the zone number. The primary and secondary
message numbers for the selected zone will be shown as
P:nnn S:xxx
; where “nnn” and “xxx”
indicates the primary and secondary message numbers being played (Fire message = 1-16, MNS
message = 101-116).
•
Row C (Silence) – Indicates the silence status of the emergency communication system
(
ON/OFF
).
•
Row C (City) – Indicates the active city code being used by the voice system (if applicable). Valid
city code must be set in the panel’s configuration menus for this option to be visible.
•
Row D (MNS Reset) – Displays the MNS RESET countdown time.
•
Row D (Disable) – Displays the ENABLE or DISABLE status of the MNS RESET feature.