Chapter 8 System Operation
PAGE 8- 51
8-7-8
Fastening Parameters (Revolutions / Number of Rotations / Current)
D-No.500
Freerun Revolutions
[rev]
Setting Range
:
0
~
99.9
Set the number of revolutions before D-No.401 [Freerun Speed] is switched to D-No.402 [1
ST
Speed].
Even if the Freerun Speed Revolution is not reached, it switches to D-No.402 [1
ST
Speed] when the
D-No.104 [Ramp Down Start Torque] is detected.
D-No.501
Reverse 2 Revolutions
[rev]
Setting Range
:
0
~
99.9
Used for D-No.002 [Fastening Option]
:
[Reverse Before Fastening]. Also it is used for fastening sequence
command [Reverse 2].
D-No.502
Reverse 3 Revolutions
[rev]
Setting Range
:
0
~
99.9
Used for fastening sequence command [Reverse 3].
D-No.503
Rundown Revolution Low Limit
[rev]
D-No.504
Rundown Revolution High Limit
[rev]
Setting Range:0
~
99.9
Set the high and low limits of the number of rotated revolutions from the beginning of the fastening to the
end.
When the number of rotations exceeds the D-No.504 [Rundown Revolution High Limit] at the time of
fastening end, or if D-No.503
「
Rundown Revolution Low Limit
」
is not reached, the fastening result will be
REJECT.
D-No.505
Offset Check Revolutions
[rev]
Setting Range
:
0
~
99.9
Used for D-No.002 [Fastening Option]
:
[Reverse Before Fastening]. Also it is used for fastening sequence
command [Reverse 2].
D-No.520
Full Scale Current
[A]
D-No.521
Low Current Limit
[A]
D-No.522
High Current Limit
[A]
D-No.523
Fastening Current Limit
[A]
Setting Range
:
0
~
Due to controller type
Set the values below according to the combination of controller type and tool type.
Controller
Type
Tool Type
D-No.520
Full Scale
Current [A]
D-No.521
Low Current
Limit [A]
D-No.522
High Current
Limit [A]
D-No.523
Fastening
Current Limit [A]
MFC-S024
CFT-
□□□
RS1-
□
24.0
0.0
24.0
24.0
MFC-S060
CFT-
□□□
RS3-
□
60.0
0.0
60.0
60.0
MFC-S120
CFT-
□□□
RS4-
□
120.0
0.0
120.0
120.0
When the actual fastening current falls outside the range defined by D-No. 521 “Low Current Limit” and
D-No. 522 “High Current Limit,” although the Unit outputs the ACCEPT fastening judgment, the PLC
output layout output signal “Multi: Current Limit Warning,” “Axis: Low Current Value Limit Warning,” “Axis:
High Current Limit Value Warning,” or “Current Limit Warning” to “ON.”
Содержание AFC3000
Страница 1: ...AFC3000E HW 1 ...
Страница 17: ......
Страница 18: ...Chapter 1 Outline PAGE 1 1 Chapter 1 Outline 1 ...
Страница 25: ......
Страница 26: ...Chapter 2 Specifications PAGE 2 1 Chapter 2 Specifications 2 ...
Страница 34: ...Chapter 3 System Description PAGE 3 1 Chapter 3 System Description 3 ...
Страница 64: ...Chapter 4 Installation and Wiring PAGE 4 1 Chapter 4 Installation and Wiring 4 ...
Страница 131: ...Chapter 4 Installation and Wiring PAGE 4 68 Blank Page ...
Страница 132: ...Chapter 5 I O Expansion Unit Page 5 1 Chapter 5 I O Expansion Unit 5 ...
Страница 164: ...Chapter 6 Power up and Initial Checks PAGE 6 1 Chapter 6 Power Up and Initial Checks 6 ...
Страница 168: ...Chapter 7 Fastening Instructions PAGE 7 1 Chapter 7 Fastening Instructions 7 ...
Страница 207: ... Blank Page ...
Страница 208: ...Chapter 8 System Operation PAGE 8 1 Chapter 8 System Operation 8 ...
Страница 259: ...Chapter 8 System Operation PAGE 8 52 ...
Страница 260: ...Chapter 9 Maintenance Inspection PAGE 9 1 Chapter 9 Maintenance Inspection 9 ...
Страница 268: ...Chapter 10 Troubleshooting PAGE 10 1 Chapter 10 Troubleshooting 10 ...
Страница 294: ......