Installation
Hauser
15
3.2.5
Inlet and outlet runs
If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc. The
longest inlet and outlet run must be taken into consideration if two or more flow obstructions are
present. The following inlet and outlet runs are recommended to comply with measuring accuracy
specifications:
A0014016
Fig. 10:
Inlet and outlet runs (side view)
1
Valve (2/3 open)
2
Pump
3
Two pipe bends in different directions
3.2.6
Vibrations
Secure the piping and the sensor if vibration is severe.
Information on resistance to vibration and shock is provided on Page 82.
A0008750
Fig. 11:
Measures to prevent device vibrations
10 x DN
20 x DN
15 x DN
10 x DN
3 x DN
1
2
3
> 10 m (33 ft)