Troubleshooting
Proline Prosonic Flow 93C FOUNDATION Fieldbus
68
Hauser
694
Device status message (FF):
Simulation of measuring CH1
active - Err. No. 694
Local display:
S: SIM. MEASUR. CH1
$
: # 694
BLOCK_ERR = Simulation
active
OUT. QUALITY = UNCERTAIN
Cause:
Simulation is active.
Remedy:
Switch off simulation:
• FF: Transducer Block "Transducer_CH1"
(base index: 1400) or Transducer Block
"Transducer_CH2" (base index: 1500)
→
Parameter "Simulation - Measurand"
→
OFF
• Local display: SUPERVISION
→
SYSTEM
→
OPERATION
→
SIM. MEASURAND (
→
OFF)
Transducer_Error = No Error
OUT. SUBSTATUS = Non specific
695
Device status message (FF):
Simulation of measuring CH2
active - Err. No. 695
Local display:
S: SIM. MEASUR. CH2
$
: # 695
BLOCK_ERR = Simulation
active
OUT. QUALITY = UNCERTAIN
Transducer_Error = No Error
OUT. SUBSTATUS = Non specific
No. # 7xx
→
Application error
743
Device status message (FF):
Zero point adjustment CH1 is
not possible – Err. No. 743
Local display:
S: 0-ADJ. FAIL CH1
$
: # 743
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = UNCERTAIN
Cause:
The medium velocity has exceeded a value of
0.1 m/s.
Remedy:
Check whether all prerequisites for carrying out a
zero point adjustment have been met.
Transducer_Error = No Error
OUT. SUBSTATUS = Non specific
744
Device status message (FF):
Zero point adjustment CH2 is
not possible – Err. No. 744
Local display:
S: 0-ADJ. FAIL CH2
$
: # 744
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = UNCERTAIN
Transducer_Error = No Error
OUT. SUBSTATUS = Non specific
–
No communication to
amplifier
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Communication error. No communication with
measuring amplifier.
Remedy:
1.
Switch power supply off and on again.
2.
Check whether the electronics boards are
correctly inserted in their holders
Transducer_Error = General
Error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
No.
Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Transducer Block
error messages
"Diagnosis" Transducer
Block
Analog Input Function Block
error messages
Reason for error/rectification
(spare parts
→
ä
71)