Troubleshooting
Proline Prosonic Flow 93C FOUNDATION Fieldbus
66
Hauser
261
Device status message (FF):
Communication failure
amplifier –
Err. No. 261
Local display:
S: COMMUNICAT. I/O
$
: # 261
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Communication error. No data reception between
amplifier and I/O board or faulty internal data
transfer.
Remedy:
Check whether the electronics boards are correctly
inserted in their holders
Transducer_Error = Electronics
failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
No. # 3xx
→
System limits exceeded
392
Device status message (FF):
Attenuation of acoustic
measurement section too high
CH1 –
Err. No. 392
Local display:
S: SIGN. LOW CH1
$
: # 392
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Attenuation of acoustic measurement section too
high.
Remedy:
1.
Check to see if the coupling fluid must be
renewed.
2.
It is possible that the fluid indicates too much
attenuation.
3.
It is possible that the pipe indicates too much
attenuation.
4.
Check the sensor spacing (Installation
dimensions).
5.
Reduce the number of traverses if possible.
Transducer_Error =
Mechanical failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
393
Device status message (FF):
Attenuation of acoustic
measurement section too high
CH2 –
Err. No. 393
Local display:
S: SIGN. LOW CH2
$
: # 393
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Transducer_Error =
Mechanical failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
No. # 5xx
→
Application error
501
Device status message (FF):
Download device software
active –
Err. No. 501
Local display:
S: SW.-UPDATE ACT.
!: # 501
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
New amplifier or communication software version
is being loaded to the device.
Currently no other functions are possible.
Remedy:
Wait until process is finished. The device will
restart automatically.
Transducer_Error = General
Error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
502
Device status message (FF):
Up-/Download device software
active –
Err. No. 502
Local display:
S: UP-/DOWNLO. ACT.
!: # 502
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Uploading or downloading the device data via
operating program. Currently no other functions
are possible.
Remedy:
Wait until process is finished.
Transducer_Error = General
Error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
No.
Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Transducer Block
error messages
"Diagnosis" Transducer
Block
Analog Input Function Block
error messages
Reason for error/rectification
(spare parts
→
ä
71)