Proline Prosonic Flow 93C FOUNDATION Fieldbus
Wiring
Hauser
31
A0014580
Fig. 19:
Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(14 AWG)
a
Connection compartment cover
b
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L
−
for DC
c
Ground terminal for protective ground
d
Fieldbus cable:
Terminal No. 26: FF + (with reverse polarity protection)
Terminal No. 27: FF – (with reverse polarity protection)
e
Ground terminal for signal cable shield
Observe the following:
– the shielding and grounding of the fieldbus cable
– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f
Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)
FF (–)
FF (+)
1
2
f
22 23
20 21
24 25 26 27
a
L1
N
c
e
b
b
d
d
(L+)
(L–)