Proline Prosonic Flow 93C FOUNDATION Fieldbus
Operation
Hauser
43
5.5
Operating options
5.5.1
Operating program "FieldCare"
FieldCare is Hauser’s FDT-based plant asset management tool and allows the configuration
and diagnosis of intelligent field devices. By using status information, you also have a simple but
effective tool for monitoring devices. The Proline flowmeters are accessed via a service interface or
via the service interface FXA193.
5.5.2
Operating via FOUNDATION Fieldbus configuration programs
The user can obtain special configuration and operating programs offered by the different
manufacturers for use in configuration. These can be used for configuring both the FOUNDATION
Fieldbus functions and all the device-specific parameters. The predefined Function Blocks allow
uniform access to all the network and fieldbus device data.
A step-by-step description of the procedure for commissioning the FF functions is given on
along with the configuration of device-specific parameters.
General information on FOUNDATION Fieldbus is provided in the Operating Instructions
"FOUNDATION Fieldbus Overview" (BA013S) acquired at:
→
www.endress.com
→
Download.
System files
You will need the following files for commissioning and network configuration:
• Commissioning
→
Device description (Device Description: *.sym, *.ffo)
• Network configuration
→
CFF file (Common File Format: *.cff)
You can obtain these files as follows:
• Free of charge via the Internet
→
www.endress.com
• From Hauser stating the order number (No. 56003896)
• Via the Fieldbus Foundation Organization
→
www.fieldbus.org
!
Note!
Ensure you use the correct system files for linking the field devices into the host system. Appropriate
version information can be called up via the following functions/parameters:
Local display:
• HOME
→
BASIC FUNCTIONS
→
FOUND. FIELDBUS
→
INFORMATION
→
DEVICE REVISION (6243)
• HOME
→
BASIC FUNCTIONS
→
FOUND. FIELDBUS
→
INFORMATION
→
DD REVISION (6244)
FOUNDATION Fieldbus interface
• Resource Block
→
Parameter DEV_REV
• Resource Block
→
Parameter DD_REV
Example (with local display):
Display in the DEVICE REVISION (6243) function
→
03
Display in the DD REVISION (6244) function
→
01
Device description file (DD) required
→
0301.sym / 0301.ffo