Proline Prosonic Flow 93C FOUNDATION Fieldbus
Troubleshooting
Hauser
63
9.2.1
List of system error messages
No.
Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Transducer Block
error messages
"Diagnosis" Transducer
Block
Analog Input Function Block
error messages
Reason for error/rectification
(spare parts
* With FOUNDATION Fieldbus, error messages are displayed in the "Diagnosis" Transducer Block (base index: 1600) by means of the
"Diag. – Act.Sys.Condition" parameter (manufacturer-specific).
S = System error
$
= Fault message (with an effect on operation)
! = Notice message (without any effect on operation)
No. # 0xx
→
Hardware error
001
Device status message (FF):
ROM/RAM Failure –
Err. No. 001
Local display:
S: CRITICAL FAILURE
$
: # 001
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
ROM/RAM error. Error when accessing the
program memory (ROM) or random access
memory (RAM) of the processor.
Remedy:
Replace the amplifier board.
Transducer_Error = Electronics
failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
011
Device status message (FF):
Amplifier EEPROM failure –
Err. No. 011
Local display:
S: AMP HW EEPROM
$
: # 011
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Amplifier with faulty EEPROM
Remedy:
Replace the amplifier board.
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
012
Device status message (FF):
Amplifier EEPROM data
inconsistent –
Err. No. 012
Local display:
S: AMP SW EEPROM
$
: # 012
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Error when accessing data of the measuring
amplifier EEPROM
Remedy:
Perform a "warm start" (= start the measuring
system without disconnecting main power).
– FF: "Diagnosis" Transducer Block
(base index: 1600)
→
"Sys. – Reset" parameter
RESTART SYSTEM
– Local display: SUPERVISION
→
SYSTEM
→
OPERATION
→
SYSTEM RESET
(
→
RESTART SYSTEM)
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
041
Device status message (FF):
T-DAT failure –
Err. No. 041
Local display:
S: TRANSM. HW-DAT
$
: # 041
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause
:
1.
T-DAT is not plugged into the amplifier board
correctly (or is missing).
2.
T-DAT is defective.
Remedy:
1.
Check whether the T-DAT is correctly plugged
into the amplifier board.
2.
Replace the T-DAT if it is defective.
Check that the new, replacement DAT is
compatible with the measuring electronics.
Check the:
- Spare part set number
- Hardware revision code
3.
Replace measuring electronic boards if
necessary.
4.
Plug the T-DAT into the amplifier board.
Transducer_Error = Electronics
failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
042
Device status message (FF):
T-DAT data inconsistent –
Err. No. 042
Local display:
S: TRANSM. SW-DAT
$
: # 042
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)