Proline Prosonic Flow 93C FOUNDATION Fieldbus
Troubleshooting
Hauser
61
Transducer Block: The
manufacturer-specific
parameters are not visible.
(continued)
The device description file (Device Description, DD) has not been loaded into the host
system or the configuration program
→
Load the file into the configuration system.
!
Note!
Ensure you use the correct system files for linking the field devices into the host system.
Appropriate version information can be called up in the measuring device via the following
functions/parameters:
Local display:
• HOME
→
BASIC FUNCTIONS
→
FOUND. FIELDBUS
→
INFORMATION
→
DEVICE REVISION (6243)
• HOME
→
BASIC FUNCTIONS
→
FOUND. FIELDBUS
→
INFORMATION
→
DD REVISION (6244)
FF configuration program:
• Resource Block
→
Parameter DEV_REV
• Resource Block
→
Parameter DD_REV
Example (local display): Display in the DEVICE REVISION (6243) function
→
03
Display in the DD REVISION (6244) function
→
01
Required device description file (DD)
→
0301.sym / 0301.ffo
Analog Input Function
Block: The output value
OUT is not updated despite
having a GOOD status.
Simulation is active
→
Deactivate simulation via parameter group SIMULATE.
Error messages
Error messages in the FF configuration program
Error messages on the local display
Æ
Other error (without error message)
Some other error has
occurred.