AX100-Series - Installing a Fibre Channel Storage System with a Direct Connection to a NetWare Server
Connecting ac Power to an AX100 Storage System
If You Need to Power Down the Storage System
For an orderly shutdown that protects your cache data, use the
storage-system power button. The storage system takes a full minute
to power down
after
you press the power button. So after powering
down the storage system, wait one minute before powering it on
again. If storage-system power is turned off by the power button or
by a software shutdown, you must press the power button to
re-apply power. If you power down the storage system by
unplugging the power cord, the storage system powers up as soon as
it is reconnected to the ac power source.
What Next?
Go to
Connecting the Storage-System Management Ports
Connecting ac Power to an AX100 Storage System
Read this section if you are connecting power to anAX100 (dual-SP)
storage system. If you are connecting power to an AX100SC
(single-SP) storage system, go to
Connecting ac Power to an AX100SC
Before You Start
To complete this procedure, you need
❑
The serial cable that shipped with the UPS. This cable allows
Navisphere Express to monitor UPS status. You may also need an
RJ45-DB9 adapter cable that shipped in the AX100-Series
accessory box to connect the UPS serial cable to the storage
system.
❑
The ac power cables appropriate to your power source. These
cables shipped with the storage system.