Configuration
86 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
The power feedback unit reacts in different ways on phase failures. One possibility is the
"2 phase operation", the other one let the system get out of operation and the collective-
error-relay signals the failure.
Coding via jumper, see figure 4.4.4.1.1:
J3 J5 J6 J7 Phase-failure-supervision
— 0 0 — Sensitive, error storage "ON"
0 Jumper open
— — — — Insensitive, error storage "ON"
— Jumper closed
0 X X — Off, but error storage "ON"
X Jumper random
0 X X 0 Off, error storage "OFF"
Note:
Jumper J7 only exists from version 1.4.2 of the control board. Error storage "ON" means that the
error "phase failure" is shown via LED until you confirm. Error storage "OFF" how-ever means
that the error "phase failure" is shown via LED only as long as the failure really exists.
Danger!
Pull off the jumper J3 is only allowed by interrupting the pulses of the frequency inverter or of
the power feedback unit in the case of switching off the mains by series interrupting devices like
contactors, main switches or any others. This is necessary to stop the power feedback to prevent
a dangerous voltage rise on devices in the sector where the power is switched-off. The Jumper J7
should only be removed in the case of Jumper J3 is removed. Otherwise when the phase-failure-
supervision is active a "phase failure" will only be shown as long as the failure exists (no error
storage).
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...