Technical data
Operating instructions RLD 37
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
3.6
Harmonic filter module RHF-RA module
To decrease the low frequency harmonic back effects to mains a filter module REVCON
RHF-RA can be connected to the power feedback unit according figure 4.4.1.2 and
4.4.1.3.* In the tables 3.6.1.1 and 3.6.1.2 the corresponding filter modules are listed for the
power feedback unit. Provided that the total harmonic distortion of the unaffected mains
voltage THD U is smaller as 2% and the ratio of short circuit power and installed power
R
SCE
is at least 66, the THD I of the mains current of the power feedback unit is reduced to
typical 16%.
*
Only in connection with option EST
REVCON
®
- type
Ordering code
RHF- module
REVCON
®
-
item number
Case type
Fan
RLD-E0 24-400-50-0-A RHF-RA 29-400-50-20-A
25070004
X3
inside
RLD-E0 32-400-50-0-A RHF-RA 43-400-50-20-A
25070007
X3
inside
RLD-E0 40-400-50-0-A RHF-RA 58-400-50-20-A
25070008
X4
inside
RLD-E0 48-400-50-0-A RHF-RA 58-400-50-20-A
25070008
X4
inside
RLD-E0 58-400-50-0-A RHF-RA 72-400-50-20-A
25070009
X4
inside
RLD-E0 80-400-50-0-A RHF-RA 101-400-50-20-A
25070011
X5
inside
RLD-E0 95-400-50-0-A RHF-RA 144-400-50-20-A
25070012
X6
inside
RLD-E0 116-400-50-0-A RHF-RA 144-400-50-20-A
25070012
X6
inside
RLD-E0 140-400-50-0-A RHF-RA 180-400-50-20-A
25070013
X6
inside
RLD-E0 170-400-50-0-A RHF-RA 217-400-50-20-A
25070014
X7
inside
RLD-E0 200-400-50-0-A RHF-RA 252-400-50-20-A
25070015
X7
inside
RLD-E0 230-400-50-0-A RHF-RA 304-400-50-20-A
25070016
X7
inside
RLD-E0 265-400-50-0-A RHF-RA 304-400-50-20-A
25070016
X7
inside
RLD-E0 300-400-50-0-A RHF-RA 380-400-50-20-A
25070018
X7
inside
RLD-E0 345-400-50-0-A RHF-RA 433-400-50-20-A
25070019
X8
inside
Table 3.6.1.1
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...