Technical data
34 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
DC- fuses REVCON RLD E0
It is recommended to protect the power feedback unit is equipped with semiconductor fus-
es according to the following tables (refer to figure 4.4.1.1 position 9). The listed manufac-
turer is recommended, but naturally also comparative fuses of other manufacturer (e.g.
Jean Müller, Ferraz, and Bussmann) are suitable.
Stop!
If semiconductor fuses trip, please get in contact with ELTROPLAN-REVCON immediately, as
possibly further protective measures have tripped. If fuses are exchanged, please verify that only
the original types are used for replacement.
Danger!
Before replacing a fuse, switch off all voltages!
REVCON
®
- type
DC-fuses
(use fast acting semiconductor fuses only)
RLD-E0 10-500-50/60-0-A
Siba 5012406.20 20A 690V 10x38mm
RLD-E0 15-500-50/60-0-A
Siba 5017906.30 30A 690V 14x51mm
RLD-E0 20-500-50/60-0-A
Siba 5012406.50 50A 690V 14x51mm
RLD-E0 25-500-50/60-0-A
Siba 5012406.50 50A 690V 14x51mm
RLD-E0 30-500-50/60-0-A
Siba 5012406.50 50A 690V 14x51mm
RLD-E0 40-500-50/60-0-A
Siba 5014006.100 100A 690V 22x58mm
RLD-E0 50-500-50/60-0-A
Siba 5014006.100 100A 690V 22x58mm
RLD-E0 60-500-50/60-0-A
Siba 2018920.160 160A 690V NH 00
RLD-E0 73-500-50/60-0-A
Siba 2018920.160 160A 690V NH 00
RLD-E0 88-500-50/60-0-A
Siba 2018920.200 200A 690V NH 00
RLD-E0 100-500-50/60-0-A
Siba 2018920.315 315A 690V NH 00
RLD E0-120-500-50/60-0-A
Siba 2018920.250 250A 690V NH 00
RLD-E0 145-500-50/60-230/115-A
Siba 2018920.315 315A 690V NH 00
RLD-E0 175-500-50/60-230/115-A
Siba 2071332.400 400A 1100V NH 01
RLD E0-213-500-50/60-230/115-A
Siba 2071332.500 500A 690V SQB 1
RLD-E0 250-500-50/60-230/115-A
Siba 2071332.500 500A 1100V NH 01
RLD-E0 288-500-50/60-230/115-A
Siba 2071332.630 630A 1100V NH 01
RLD-E0 331-500-50/60-230/115-A
Siba 2071332.630 630A 1100V NH 01
RLD-E0 375-500-50/60-230/115-A
Siba 2071332.630 630A 1100V NH 01
RLD E0-431-500-50/60-230/115-A
Siba 20 723 32.800 800A 690V SQB 2
Table
3.4.3
Stop!
In case that the installation must be UL-compliant, UL R/C special purpose semiconductor fuses,
cat. No. 2072XZ, manufactured by SIBA, must be used as well for AC as for DC protection.
STOP
STOP
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...