Electrical Installation
Operating instructions RLD 67
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Legend for figure 4.4.1.2 (REVCON
RLD E0 with RHF-RA)
1.
Fusing in accordance with controller manual.
2.
It is not allowed to connect any other devices except the frequency inverter and the power
feedback unit behind the main magnetic switch.
Danger!
If this is not observed, you take the risk that, in the case of switching off the mains during feed-
back the power, the voltage in that sector may rise up to a dangerous level. This may destroy the
connected devices and perhaps also the inverter and/or the power feedback unit. To avoid such
situation, the power feedback unit is equipped with an overvoltage switch off, but nevertheless
this hint should be observed!
3.
RHF-RA module
4.
Cross section in accordance with the relevant VDE-rules.
5.
Beginning with enclosure 2: Fusing (Supply, <2A current input) in accordance with DIN
VDE 0298 or short circuit proof wiring.
6.
RFI filter, optional:
At RFI-filter installation size RFI-RA01 is the connection to the power feedback module
realized by a PG-screw connection. This connection of the RFI-filter must occur phase
correct over the terminals -From Supply-. The terminals -To Inverter- must be open.
7.
At these terminals one or more controllers (even with different power ratings) may be at-
tached, like it shown in figure
4.5.1. Even if several controllers are attached, the wires
have to be as
short and low impedance
as possible!
8.
DC fuses: The power feedback is not equipped with DC fuses.
9.
The possibility of an external „OFF“ by the terminals 7 and 8:
These terminals may be used for an external
OFF
-signal (NOC, short time contact) to
stop the power feedback unit.
10.
The „ON“ or „RESET“ signal may be initiated via terminals 11 and 12:
Terminals 11 and 12: Positive pulse (12-24 V DC); practicable e.g. via PLC (terminal 11
+, terminal 12 -).
11.
Fan supply: The power feedback modules beginning with enclosure 2/701 require the in
the ordering code specified auxiliary voltage (230V or 115V).
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...