Electrical Installation
Operating instructions RLD 75
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Terminal 5
External Reset: Applying a DC voltage of 15-27V starts the inverter after it was stopped by
a fault. Without voltage applied status of the unit stays unchanged.
Terminal 6
Currently not used
Terminal 7
Status output: If the unit is in operation without any fault, output will show 24VDC. In
case of a fault or at no operation, output will be 0V.
Terminal 8
Input 24V DC to supply status output: Output at terminal 7 will ONLY work if terminal 8
is supplied by 24VDC. Leaving terminal 8 without supply, operation of the unit is not in-
terfered, but no status output will be possible.