Operation on a transformer
Is the energy balance of an installation negative (e.g. for a period more braking energy is
created then consumed on the secondary side of the transformer), the nominal (complex)
power of the transformer must be at least 1,5 times higher than the regenerated braking
power.
Generally the short circuit voltage of the transformer should be preferably small (typical 4-
6%).
Danger!
At non-observance of these connecting conditions overvoltage and mains voltage harmonic dis-
tortions are generated, which can lead to damages at the power feedback units and other con-
nected components!
Die above-named conditions are in the in figure 2.5.2 diagrammed mains section just ob-
served, if the other loads are switched off.
M
M
R
Tr
10kV
0,4kV
100kVA
60kW
20kW
20kW
FC
REVCON
Figure 2.5.2
The mains impedance of all installed feedback units should be 2 times so large as the
mains impedance, but minimum the 1,5-times of the mains impedance!
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...