Electrical Installation
Operating instructions RLD 63
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Connection
All connections should be as short and low-impedance as possible.
For the observance of the EMC-guideline (in accordance to actual standards like VDE
0160 and EN 50178) screened wires have to be used.
Connect the mains supply wires at the terminals L1, L2, L3 (at the mains choke) of the
power feedback unit. Only three phase connection is allowed.
A defined phase sequence (clockwise rotation field) must be observed at the main circuit
connection of the power unit. The power feedback unit is equipped with a phase-sequence
control unit. In case of an incorrect rotation field an error message is displayed via LED as
follows: "rotation field failure" or "phase failure". In this case two phases, connected to the
power unit, have to be exchanged.
Connect the earthing wire of the supply cables to the earthing screw of the power feedback
unit.
The wires for the DC-bus coupling between controller and power feedback unit have to be
connected to the DC terminals. It is absolutely necessary to observe the correct polarity.
Danger!
An interchanging of + (PLUS) and – (MINUS) avoids the correct function of the power feedback
unit.
Danger!
It is in no case allowed to pre-connect not current compensated direct inductances!
Содержание REVCON RLD
Страница 46: ...Installation Operating instructions RLD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 0 340 ...
Страница 47: ...Installation 46 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 0 341 ...
Страница 48: ...Installation Operating instructions RLD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 0 400 ...
Страница 49: ...Installation 48 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 1 501 ...
Страница 50: ...Installation Operating instructions RLD 49 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 2 701 ...
Страница 51: ...Installation 50 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Enclosure 3 800 ...
Страница 52: ...Installation Operating instructions RLD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 8 Enclosure 3 801 ...