NOTES:
• If you are entering negative Limits, be aware that the negative value affects the
way the above and below Limits function, since negative numbers are processed as
signed values.
• If the Above Return Hysteresis is greater than the Above Setpoint, the Above Limit
is Disabled; if the Below Return Hysteresis is less than the Below Setpoint, the
Below Limit is Disabled. You may want to use this feature to disable either Above or
Below Limit conditions for a reading.
IMPORTANT! When you finish making changes to the Device Profile, click Update
Device to send the new Profile settings to the meter.
NOTE: Refer to Chapter 5 of the Communicator EXT User Manual for additional
instructions on configuring the Shark® 200S meter settings, including Time Setting,
Transformer and Line Loss Compensation, CT and PT Compensation, Secondary
Voltage display, Symmetrical Components, Voltage and Current Unbalance, and
scaling Primary readings for use with DNP.