C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 20 - Binary Counters (Primary Readings) - Read via Class 0 or with
qualifier 0, 1, 2, or 6
Object 30 - Analog Inputs (Secondary Readings) - Read via Class 0 or with
qualifier 0, 1, 2, or 6
12
2
1
Reset Demand
Counters (Max
/ Min)
N/A
N/A
N/A
none
Responds to Function 5
(Direct Operate), Quali-
fier Code 17x or 28x,
Control Code 3, Count 0,
On 0 msec, Off 1 msec
ONLY.
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
20
0
5
W-hours,
Positive
UINT32
0 to
99999999
Multiplier =
10(n-d),
where n and d
are derived
from the
energy format.
n = 0, 3, or 6
per energy
format scale
and d =
number of
decimal
places.
Whr
example:
energy format =
7.2K and W-
hours counter =
1234567 n=3 (K
scale), d=2 ( 2
digits after deci-
mal point), mul-
tiplier = 10(3-2)
= 101 = 10, so
energy is
1234567 * 10
Whrs, or
12345.67 KWhrs
20
1
5
W-hours,
Negative
UINT32
0 to
99999999
Whr
20
2
5
VAR-hours,
Positive
UINT32
0 to
99999999
VARhr
20
3
5
VAR-hours,
Negative
UINT32
0 to
99999999
VARhr
20
4
5
VA-hours,
Total
UINT32
0 to
99999999
VAhr
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
30
0
4
Meter Health
sint16
0 or 1
N/A
None
0 = OK
30
1
4
Volts A-N
sint16
0 to 32767
(150 / 32768)
V
Values above
150V
secondary
read 32767.
30
2
4
Volts B-N
sint16
0 to 32767
(150 / 32768)
V
30
3
4
Volts C-N
sint16
0 to 32767
(150 / 32768)
V
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments