B: Modbus Map and Retrieving Logs
Doc# E149721 MM-10
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
Units or Resolution
Comments
# Reg
Modbus Address
Hex
Decimal
2123
-
2125
8484 -
8486 Negative VARs, Phase B, Min Avg Dmd
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2126
-
2128
8487 -
8489 Negative VARs, Phase C, Min Avg Dmd
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2129
-
212B
8490 -
8492 VAs, Phase A, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
212C
-
212E
8493 -
8495 VAs, Phase B, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
212F
-
2131
8496 -
8498 VAs, Phase C, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2132
-
2134
8499 -
8501 Positive PF, Phase A, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2135
-
2137
8502 -
8504 Positive PF, Phase B, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2138
-
213A
8505 -
8507 Positive PF, Phase C, Min Avg Dmd Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
213B
-
213D
8508 -
8510 Negative PF, Phase A, Min Avg Dmd Timestamp TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
213E
-
2140
8511 -
8513 Negative PF, Phase B, Min Avg Dmd Timestamp TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2141
-
2143
8514 -
8516 Negative PF, Phase C, Min Avg Dmd Timestamp TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2144
-
2146
8517 -
8519 Reserved
3
2147
-
2149
8520 -
8522 Reserved
3
214A
-
214C
8523 -
8525 Reserved
3
214D
-
214F
8526 -
8528 Reserved
3
2150
-
2152
8529 -
8531 Reserved
3
2153
-
2155
8532 -
8534 Reserved
3
2156
-
2158
8535 -
8537 Symmetrical Comp Magnitude, 0 Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2159
-
215B
8538 -
8540 Symmetrical Comp Magnitude, + Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
215C
-
215E
8541 -
8543 Symmetrical Comp Magnitude, - Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
215F
-
2161
8544 -
8546 Symmetrical Comp Phase, 0 Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2162
-
2164
8547 -
8549 Symmetrical Comp Phase, + Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2165
-
2167
8550 -
8552 Symmetrical Comp Phase, - Seq, Min
Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2168
-
2170
8553 -
8555 Unbalance, 0 Seq, Min Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2171
-
2173
8556 -
8558 Unbalance, - Seq, Min Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2174
-
2176
8559 -
8561 Current Unbalance, Min Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
Block
Size:
162
read-only
230F
-
2310
8976 -
8977 Volts A-N, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
2311
-
2312
8978 -
8979 Volts B-N, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
2313
-
2314
8980 -
8981 Volts C-N, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
2315
-
2316
8982 -
8983 Volts A-B, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
2317
-
2318
8984 -
8985 Volts B-C, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
2319
-
231A
8986 -
8987 Volts C-A, previous Demand interval Short Term
Maximum
FLOAT
0 to 9999 M
volts
Short term Primary Maximum Block
Maximum instantaneous value measured during the
demand interval before the one most recently completed.