B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Alarm Log Record uses 16 bytes, 10 bytes of which are available when the log is
retrieved.
The limit # byte is broken into a type and an ID.
3.
Historical Log 1 (2)
: The Historical Log records the values of its assigned regis-
ters at the programmed interval.
NOTE:
See Section B.5.3, Number 1, for details on programming and interpreting the
log.
4.
Historical Log 2 (3)
: Same as Historical Log 1.
5.
Historical Log 3 (4)
: Same as Historical Log 1.
B.5.3: Block Definitions
This section describes the Modbus Registers involved in retrieving and interpreting a
Shark® 200S Meter Log. Other sections refer to certain 'values' contained in this sec-
tion. See the corresponding value in this section for details.
NOTES:
• “Register” is the Modbus Register Address in 0-based Hexadecimal notation. To
convert it to 1-based decimal notation, convert from hex16 to decimal10 and add
1. For example: 0x03E7 = 1000.
• “Size” is the number of Modbus Registers (2 byte) in a block of data.
Historical Log Programmable Settings:
Byte
0
1
2
3
4
5
6
7
8
9
Value
timestamp
direction
limit#
Value%
Bit
0
1
2
3
4
5
6
7
Value
type
0
0
0
0
Limit ID
Byte
0
1
2
3
4
5
6
-
-
N
Value
timestamp
values . . .