![Electro Industries Shark 200S Скачать руководство пользователя страница 146](http://html.mh-extra.com/html/electro-industries/shark-200s/shark-200s_installation-and-operators-manual_2379717146.webp)
Doc
#
E149721
B - 10
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• Max Records: The maximum number of records the log can hold given the record
size, and sector allocation. The data type is an unsigned integer from 0 - 2^32.
• Records Used: The number of records stored in the log. This number will equal the
Max Records when the log has filled. This value will be set to 1 when the log is
reset. The data type is an unsigned integer from 1 - 2^32.
NOTE:
The first record in every log before it has rolled over is a "dummy" record,
filled with all 0xFF's. When the log is filled and rolls over, this record is overwritten.
• Record Size: The number of bytes in this record, including the timestamp. The data
type is an unsigned integer in the range of 14 - 242.
• Log Availability: A flag indicating if the log is available for retrieval, or if it is in use
by another port.
0
Log Available for retrieval
1
In use by COM1 (IrDA)
2
In use by COM2 (RS485)
0xFFFF
Log Not Available - the log cannot be retrieved.
This indicates that the log is disabled.
NOTE:
To query the port by which you are currently connected, use the Port ID
register:
Register:
0x1193
Size:
1 register
8-9
Record Size in Bytes
UINT16
4 to 250
2
10-11
Log Availability
UINT16
2
12-17
Timestamp, First Record
TSTAMP
1Jan2000 - 31Dec2099
6
18-23
Timestamp, Last Record
TSTAMP
1Jan2000 - 31Dec2099
6
24-31
Reserved
8