B: Modbus Map and Retrieving Logs
Doc# E149721 MM-14
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
Units or Resolution
Comments
# Reg
Modbus Address
Hex
Decimal
2553
-
2555
9556 -
9558 Unbalance, - Seq, Max Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
2556
-
2558
9559 -
9561 Current Unbalance, Max Timestamp
TSTAMP
1Jan2000 - 31Dec2099
1 sec
3
Block
Size:
159
write-only
4E1F
-
4E1F
20000 -
20000 Reset Max/Min Blocks
UINT16
password (Note 5)
1
4E20
-
4E20
20001 -
20001 Reset Energy Accumulators
UINT16
password (Note 5)
1
4E21
-
4E21
20002 -
20002 Reset Alarm Log (Note 21)
UINT16
password (Note 5)
1
4E22
-
4E22
20003 -
20003 Reset System Log (Note 21)
UINT16
password (Note 5)
1
4E23
-
4E23
20004 -
20004 Reset Historical Log 1 (Note 21)
UINT16
password (Note 5)
1
4E24
-
4E24
20005 -
20005 Reset Historical Log 2 (Note 21)
UINT16
password (Note 5)
1
4E25
-
4E25
20006 -
20006 Reset Historical Log 3 (Note 21)
UINT16
password (Note 5)
1
4E26
-
4E26
20007 -
20007 Reserved
1
4E27
-
4E2E
20008 -
20015 Reserved
Set to 0.
2
4E29
-
4E2A
20010 -
20011 Reserved
Reserved
2
4E2B
-
4E2B
20012 -
20012 Reserved
1
4E2C
-
4E2C
20013 -
20013 Reserved
1
4E2D
-
4E2D
20014 -
20014 Reserved
1
4E2E
-
4E2E
20015 -
20015 Reserved
1
Block
Size:
16
conditional
write
5207
-
5207
21000 -
21000 Initiate Meter Firmware Reprogramming
UINT16
password (Note 5)
1
5208
-
5208
21001 -
21001 Force Meter Restart
UINT16
password (Note 5)
causes a watchdog reset, always reads 0
1
5209
-
5209
21002 -
21002 Open Privileged Command Session
UINT16
password (Note 5)
meter will process command registers (this register
through 'Close Privileged Command Session' register
below) for 5 minutes or until the session is closed,
whichever comes first.
1
520A
-
520A
21003 -
21003 Initiate Programmable Settings Update
UINT16
password (Note 5)
meter enters PS update mode
1
520B
-
520B
21004 -
21004 Calculate Programmable Settings Checksum
(Note 3)
UINT16
0000 to 9999
meter calculates checksum on RAM copy of PS block
1
520C
-
520C
21005 -
21005 Programmable Settings Checksum (Note 3)
UINT16
0000 to 9999
read/write checksum register; PS block saved in
nonvolatile memory on write (Note 8)
1
520D
-
520D
21006 -
21006 Write New Password (Note 3)
UINT16
0000 to 9999
write-only register; always reads zero
1
520E
-
520E
21007 -
21007 Terminate Programmable Settings Update (Note
3)
UINT16
any value
meter leaves PS update mode via reset
1
520F
-
5211
21008 -
21010 Set Meter Clock
TSTAMP
1Jan2000 - 31Dec2099
1 sec
saved only when 3rd register is written
3
5212
-
5212
21011 -
21011 Reserved
Reserved
1
5213
-
5219
21012 -
21018 Reserved
Reserved
7
521A
-
521A
21019 -
21019 Close Privileged Command Session
UINT16
any value
ends an open command session
1
Block
Size:
20
read/write
658F
-
659A
26000 -
26011 Perform a Secure Operation
UINT16
encrypted command to read password or change meter
type
12
Block
Size:
12
Commands Section (Note 4)
Resets Block (Note 9)
Reply to a reset log command indicates that the
command was accepted but not necessarily that the
reset is finished. Poll log status block to determine this.
Privileged Commands Block
Encryption Block