B: Modbus Map and Retrieving Logs
Doc# E149721 MM-15
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
Units or Resolution
Comments
# Reg
Modbus Address
Hex
Decimal
write only in PS update mode
752F
-
752F
30000 -
30000 CT multiplier & denominator
UINT16
bit-mapped
dddddddd mmmmmmmm
high byte is denominator (1 or 5, read-only),
low byte is multiplier (1, 10, or 100)
1
7530
-
7530
30001 -
30001 CT numerator
UINT16
1 to 9999
none
1
7531
-
7531
30002 -
30002 PT numerator
UINT16
1 to 9999
none
1
7532
-
7532
30003 -
30003 PT denominator
UINT16
1 to 9999
none
1
7533
-
7533
30004 -
30004 PT multiplier & hookup
UINT16
bit-mapped
mmmmmmmm mmmmhhhh
mm…mm = PT multiplier (1, 10, 100, or 1000)
hhhh = hookup enumeration (0 = 3 element wye[9S], 1 =
delta 2 CTs[5S], 3 = 2.5 element wye[6S])
1
7534
-
7534
30005 -
30005 Averaging Method
UINT16
bit-mapped
--iiiiii b----sss
iiiiii = interval (5,15,30,60)
b = 0-block or 1-rolling
sss = # subintervals (1,2,3,4)
1
7535
-
7535
30006 -
30006 Power & Energy Format
UINT16
bit-mapped
ppppiinn feee-ddd
pppp = power scale (0-unit, 3-kilo, 6-mega, 8-auto)
ii = power digits after decimal point (0-3),
applies only if f=1 and pppp is not auto
nn = number of energy digits (5-8 --> 0-3)
eee = energy scale (0-unit, 3-kilo, 6-mega)
f = decimal point for power
(0=data-dependant placement,
1=fixed placement per ii value)
ddd = energy digits after decimal point (0-6)
See note 10.
1
7536
-
7536
30007 -
30007 Operating Mode Screen Enables
UINT16
bit-mapped
-------x eeeeeeee
eeeeeeee = op mode screen rows on/off, rows top to
bottom are bits low order to high order
x = set to suppress PF on W/VAR/PF screens
1
7537
-
7537
30008 -
30008 Daylight Saving On Rule
UINT16
bit-mapped
hhhhhwww -dddmmmm
applies only if daylight savings in User Settings Flags =
on; specifies when to make changeover
hhhhh = hour, 0-23
www = week, 1-4 for 1st - 4th, 5 for last
ddd = day of week, 1-7 for Sun - Sat
mmmm = month, 1-12
Example: 2AM on the 4th Sunday of March
hhhhh=2, www=4, ddd=1, mmmm=3
1
7538
-
7538
30009 -
30009 Daylight Saving Off Rule
UINT16
bit-mapped
hhhhhwww -dddmmmm
1
7539
-
7539
30010 -
30010 Time Zone UTC offset
UINT16
bit-mapped
z000 0000 hhhh hhmm
mm = minutes/15; 00=00, 01=15, 10=30, 11=45
hhhh = hours; -23 to +23
z = Time Zone valid (0=no, 1=yes)
i.e. register=0 indicates that time zone is not set while
register=0x8000 indicates UTC offset = 0
1
753A
-
753A
30011 -
30011 Clock Sync Configuration
UINT16
bit-mapped
0000 0000 mmm0 0ppe
e=enable automatic clock sync (0=no, 1=yes
Line pppp = expected frequency (0=60 Hz, 1=50 Hz)
1
753B
-
753B
30012 -
30012 Reserved
Reserved
1
753C
-
753C
30013 -
30013 User Settings 2
UINT16
bit-mapped
-------- -------s
s = display secondary volts (1=yes, 0=no)
1
Programmable Settings Section
Basic Setups Block