5.2.2: Shark® 200S Meter Device Profile Settings
NOTE: Only the basic Shark® 200S meter Device Profile settings are explained in this
manual. Refer to Chapter 5 in the Communicator EXT User Manual for detailed
instructions on configuring all settings of the meter’s Device Profile. You can view the
manual online by clicking Help>Contents from the Communicator EXT Main screen.
CT, PT Ratios and System Hookup
IMPORTANT! You have two options for entering the CT and PT settings. You can
either enter CT/PT Numerator, Denominator, and Multiplier manually (see instructions
below), or you can enter the Ratios for CT/PT Numerator and Denominator and click
the Update CT/Update PT buttons to let the software calculate the Numerator,
Denominator, and Multiplier for you. You can then empty the Ratio fields and click the
Update Ratio buttons to confirm the calculated settings: you will see the same ratios
you initially entered.
For manual entry:
CT Ratios
CT Numerator (Primary): 1 - 9999
CT Denominator (Secondary): 5 or 1 Amp
NOTE: This field is display only.