6: Ethernet Configuration
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6.3: Setting up the Ethernet Module in the Shark® 200S Meter
Below are the Factory Default settings for the Shark® 200S meter's Ethernet
Module. These are programmed into the meter before it is shipped out from the
factory. Parameters indicated in bold letters (
1, 6, 7
) may need to be altered to sat-
isfy the local Ethernet configuration requirements. Other parameters (2, 3, 4) should
not be altered.
Follow the procedure described in Section 6.4 if these Factory Default
parameters need to be restored in the meter.
1) Network/IP Settings:
Network Mode.........Wired Only
IP Address..............10.0.0.1
Default Gateway.......--- not set ---
Netmask.................255.255.255.0
2) Serial & Mode Settings:
Protocol.................Modbus/RTU,Slave(s) attached
Serial Interface...... 57600,8,N,1,RS232,CH1
3) Modem/Configurable Pin Settings:
CP0..! Defaults (In) Wired CP1..! GPIO (In) CP2..! GPIO (In)
CP3..! GPIO (In) CP4..! GPIO (In) CP5..! GPIO (In)
CP6..! GPIO (In) CP7..! GPIO (In) CP8..! GPIO (In)
CP9..! GPIO (In) CP10.! GPIO (In)
RTS Output ......... Fixed High/Active