E149721
B - 39
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Sample Historical Log 1 Record:
Historical Log 1 Record and Programmable Settings
13|01|00 01|23 75|23 76|23 77|1F 3F 1F 40|1F 41
1F 42|1F 43 1F 44|06 0B 06 0C|06 0D 06 0E|17 75|
17 76|17 77|18 67|18 68|18 69|00 00 . . . . . .
62 62 62 34 34 34 44 44 62 62 62 62 62 62 . . .
These are the These are the These are the Descriptions:
Item Values: Type and Size:
13
- # registers
01
- # sectors
01
- interval
23 75 6 2 - (SINT 2 byte) Volts A THD Maximum
23 76 6 2 - (SINT 2 byte) Volts B THD Maximum
23 77 6 2 - (SINT 2 byte) Volts C THD Maximum
1F 3F 1F 40 3 4 - (Float 4 byte) Volts A Minimum
1F 41 1F 42 3 4 - (Float 4 byte) Volts B Minimum
1F 43 1F 44 3 4 - (Float 4 byte) Volts C Minimum
06 0B 06 0C 4 4 - (Energy 4 byte) VARhr Negative Phase A
06 0D 06 0E 4 4 - (Energy 4 byte) VARhr Negative Phase B
17 75 6 2 - (SINT 2 byte) Volts A 1
st
Harmonic
Magnitude
17 76 6 2 - (SINT 2 byte) Volts A 2
nd
Harmonic
Magnitude
17 77 6 2 - (SINT 2 byte) Volts A 3
rd
Harmonic
Magnitude
18 67 6 2 - (SINT 2 byte) Ib 3
rd
Harmonic Magnitude
18 68 6 2 - (SINT 2 byte) Ib 4
th
Harmonic Magnitude
18 69 6 2 - (SINT 2 byte) Ib 5
th
Harmonic Magnitude
Sample Record
06 08 17 51 08 00|00 19|00 2F|27 0F|00 00 00 00|00
00 00 00|00 00 00 00|00 00 00 00|00 00 00 00|03 E8|
00 01|00 05|00 00|00 00|00 00 . . .
11 08 17 51 08 00 - August 23, 2011 17:08:00
00 19 - 2.5%
00 2F - 4.7%
27 0F - 999.9% (indicates the value isn’t valid)
00 00 00 00 - 0
00 00 00 00 - 0
00 00 00 00 - 0
00 00 00 00 - 0
00 00 00 00 - 0