5: Communication Installation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
NOTE: Care should be taken to c to + and - to - connections.
The Shark® 100S submeter's RS485 connection can be programmed with the
buttons on the face of the meter or by using Communicator EXT
TM
software.
Standard RS485 Port Settings*
Address: 001 to 247
Baud Rate: 9600, 19200, 38400 or 57600 Baud
Protocol: Modbus RTU, Modbus ASCII, or DNP 3.0
* With Runtime Firmware Version 26 or higher, Baud Rate settings of 1200, 2400, and
4800 and Parity settings (Even, Odd, None) are also available.
IMPORTANT! The position of Jumper 2 (JP2) must be set for either RS485 or Ether-
net communication. See the figure on the next page. You put the jumper on positions
2 and 3 for LAN (Ethernet) communication, and on 1 and 2 for RS485 communication.
Electronic Circuits
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Z K Y + - SH
Va Vb Vc Vn L1 L2 PE
RS485
Pulse Contacts
Wireless Ethernet Connection
To Other
Devices
JP2: Must be in
position 1-2 for
RS485