![Electro Industries Shark 200S Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/electro-industries/shark-200s/shark-200s_installation-and-operators-manual_2379717038.webp)
Doc
#
E149721
2 - 6
2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Input Wire Gauge:
AWG#16 - 26
Fault Withstand:
Meets IEEE C37.90.1 (Surge
Withstand Capability)
Reading:
Programmable Full Scale to any PT
Ratio
Current Inputs
Class 10:
5A Nominal, 10 Amp Maximum
Class 2:
1A Nominal, 2 Amp Secondary
Burden:
0.005VA Per Phase Max at 11 Amps
Pickup Current:
0.1% of Nominal
Connections:
Screw terminal - #6-32 screws
(Diagram 4.1)
Current Surge Withstand:
100A/10 seconds at 23
o
C
Reading:
Programmable Full Scale to any CT
Ratio
Isolation
All Inputs and Outputs are galvanically isolated and tested to 2500VAC
Environmental Rating
Storage:
(-20 to +70)
o
C
Operating:
(-20 to +70)
o
C
Humidity:
to 95% RH Non-condensing
Faceplate Rating:
NEMA12 (Water Resistant)
Содержание Shark 200S
Страница 1: ...S h a r k 200S ...
Страница 2: ...This page intentionally left blank ...