B: Modbus Map and Retrieving Logs
Doc# E149721 MM-5
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
Units or Resolution
Comments
# Reg
Modbus Address
Hex
Decimal
07F7
-
07F8
2040 -
2041 Negative VARs, Phase A, Average
FLOAT
-9999 M to +9999 M
VARs
2
07F9
-
07FA
2042 -
2043 Negative VARs, Phase B, Average
FLOAT
-9999 M to +9999 M
VARs
2
07FB
-
07FC
2044 -
2045 Negative VARs, Phase C, Average
FLOAT
-9999 M to +9999 M
VARs
2
07FD
-
07FE
2046 -
2047 VAs, Phase A, Average
FLOAT
-9999 M to +9999 M
VAs
2
07FF
-
0800
2048 -
2049 VAs, Phase B, Average
FLOAT
-9999 M to +9999 M
VAs
2
0801
-
0802
2050 -
2051 VAs, Phase C, Average
FLOAT
-9999 M to +9999 M
VAs
2
0803
-
0804
2052 -
2053 Positive PF, Phase A, Average
FLOAT
-1.00 to +1.00
none
2
0805
-
0806
2054 -
2055 Positive PF, Phase B, Average
FLOAT
-1.00 to +1.00
none
2
0807
-
0808
2056 -
2057 Positive PF, Phase C, Average
FLOAT
-1.00 to +1.00
none
2
0809
-
080A
2058 -
2059 Negative PF, Phase A, Average
FLOAT
-1.00 to +1.00
none
2
080B
-
080C
2060 -
2061 Negative PF, Phase B, Average
FLOAT
-1.00 to +1.00
none
2
080D
-
080E
2062 -
2063 Negative PF, Phase C, Average
FLOAT
-1.00 to +1.00
none
2
Block
Size:
64
read-only
0BB7
-
0BB8
3000 -
3001 Watts, 3-Ph total
FLOAT
-9999 M to +9999 M
watts
2
0BB9
-
0BBA
3002 -
3003 VARs, 3-Ph total
FLOAT
-9999 M to +9999 M
VARs
2
0BBB
-
0BBC
3004 -
3005 VAs, 3-Ph total
FLOAT
-9999 M to +9999 M
VAs
2
0BBD
-
0BBE
3006 -
3007 Power Factor, 3-Ph total
FLOAT
-1.00 to +1.00
none
2
0BBF
-
0BC0
3008 -
3009 Watts, Phase A
FLOAT
-9999 M to +9999 M
watts
2
0BC1
-
0BC2
3010 -
3011 Watts, Phase B
FLOAT
-9999 M to +9999 M
watts
2
0BC3
-
0BC4
3012 -
3013 Watts, Phase C
FLOAT
-9999 M to +9999 M
watts
2
0BC5
-
0BC6
3014 -
3015 VARs, Phase A
FLOAT
-9999 M to +9999 M
VARs
2
OBC7
-
0BC8
3016 -
3017 VARs, Phase B
FLOAT
-9999 M to +9999 M
VARs
2
0BC9
-
0BCA
3018 -
3019 VARs, Phase C
FLOAT
-9999 M to +9999 M
VARs
2
0BCB
-
0BCC
3020 -
3021 VAs, Phase A
FLOAT
-9999 M to +9999 M
VAs
2
0BCD
-
0BCE
3022 -
3023 VAs, Phase B
FLOAT
-9999 M to +9999 M
VAs
2
0BCF
-
0BD0
3024 -
3025 VAs, Phase C
FLOAT
-9999 M to +9999 M
VAs
2
0BD1
-
0BD2
3026 -
3027 Power Factor, Phase A
FLOAT
-1.00 to +1.00
none
2
0BD3
-
0BD4
3028 -
3029 Power Factor, Phase B
FLOAT
-1.00 to +1.00
none
2
0BD5
-
0BD6
3030 -
3031 Power Factor, Phase C
FLOAT
-1.00 to +1.00
none
2
0BD7
-
0BD8
3032 -
3033 W-hours, Received
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
0BD9
-
0BDA
3034 -
3035 W-hours, Delivered
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
0BDB
-
0BDC
3036 -
3037 W-hours, Net
SINT32
-99999999 to 99999999
Wh per energy format
2
0BDD
-
0BDE
3038 -
3039 W-hours, Total
SINT32
0 to 99999999
Wh per energy format
2
0BDF
-
0BE0
3040 -
3041 VAR-hours, Positive
SINT32
0 to 99999999
VARh per energy format
2
0BE1
-
0BE2
3042 -
3043 VAR-hours, Negative
SINT32
0 to -99999999
VARh per energy format
2
0BE3
-
0BE4
3044 -
3045 VAR-hours, Net
SINT32
-99999999 to 99999999
VARh per energy format
2
0BE5
-
0BE6
3046 -
3047 VAR-hours, Total
SINT32
0 to 99999999
VARh per energy format
2
0BE7
-
0BE8
3048 -
3049 VA-hours, Total
SINT32
0 to 99999999
VAh per energy format
2
0BE9
-
0BEA
3050 -
3051 W-hours, Received, Phase A
SINT32
0 to 99999999 or
Wh per energy format
2
0BEB
-
0BEC
3052 -
3053 W-hours, Received, Phase B
SINT32
0 to 99999999 or
Wh per energy format
2
0BED
-
0BEE
3054 -
3055 W-hours, Received, Phase C
SINT32
0 to 99999999 or
0
99999999
Wh per energy format
2
0BEF
-
0BF0
3056 -
3057 W-hours, Delivered, Phase A
SINT32
0 to 99999999 or
Wh per energy format
2
0BF1
-
0BF2
3058 -
3059 W-hours, Delivered, Phase B
SINT32
0 to 99999999 or
0
99999999
Wh per energy format
2
0BF3
-
0BF4
3060 -
3061 W-hours, Delivered, Phase C
SINT32
0 to 99999999 or
Wh per energy format
2
0BF5
-
0BF6
3062 -
3063 W-hours, Net, Phase A
SINT32
-99999999 to 99999999
Wh per energy format
2
* Wh received & delivered always have opposite signs
* Wh received is positive for "view as load", delivered is
positive for "view as generator"
* 5 to 8 digits
* decimal point implied, per energy format
* resolution of digit before decimal point = units, kilo, or
mega, per energy format
* see note 10
Uncompensated Readings Block
Per phase power and PF have values
only for WYE hookup and will be
zero for all other hookups.