6: Ethernet Configuration
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• The Ethernet Module in the Shark® 200S meter can be locally or remotely config-
ured using a Telnet connection over the network.
• The configuration parameters can be changed at any time and are retained when
the meter is not powered up. After the configuration has been changed and saved,
the Ethernet module performs a Reset.
• Only one person at a time should be logged into the network port used for setting
up the meter. This eliminates the possibility of several people trying to configure
the Ethernet interface simultaneously.
6.3.1: Configuring the Ethernet Module in the Shark® 200S Meter
Using Windows XP© on the Host Computer
Establish a Telnet connection to port 9999:
NOTE:
If your PC is running
Windows 7, you need to enable
Telnet before using it.
1. Open the Control Panel.
2. Select Programs and Features.
3. Select Turn Windows features
on or off.
4. Check the box for Telnet Client.
5. Click OK. The Telnet client is
now available.
1. From the Windows Start menu,
click
Run
and type 'cmd'.
2. Click the
OK
button to bring up Windows's Command Prompt window.
3. In the Command Prompt window, type:
telnet 10.0.0.1 9999
and press the
Enter
key.
NOTE:
Be sure to include a space between the IP address and 9999.