Programming Manual
2.11
Note:
The CDR-3 coder baud rate may NOT be set to 300. When the
CDR-3 and PT-1S share this port, the baud should be set to 1200.
7. Start Action
This Action will be activated upon power up of the system and will
remain activated until a manual or automatic command overrides it.
This action WILL NOT activate after a reset.
Note:
If a start action is entered, a start sequence may NOT be entered.
8. Start sequence
This sequence will begin upon power up of the system and continue
until completed, or until a manual or automatic command interrupts it.
This sequence will NOT activate after a reset.
Note:
If a start sequence is entered, a start action may NOT be entered.
9. Bell Coder = Enable/Disable
If a coder card (CDR-3) is installed in the system and connected to this
panel, this item must be enabled so that the codes will be generated.
A. Walk Test = Silent/Audible (This item is not displayed for CM2(N)
panels)
Defines the walk test feature to provide an output to the indicating
appliances upon alarm test of an initiating device. When an audible
walk test is activated, the CM1N control panel will activate action 9003
for a period of one (1) second.
B. Sys com class = A/B (This item is not displayed for CM2(N) panels)
Defines the panel-to-panel data communications class for the system.
C. Card menu (This is item "A)" for CM2N Configuration Menu)
When this menu item is selected, a window appears on the screen
allowing the programmer to assign the card types and their location in
the CM1(N) and CM2(N) modules. When selected, a new window will
be displayed as follows:
1. ZAS-1A = Class A communications for a ZAS-1 Card.
firealarmresources.com
Содержание IRC-3
Страница 1: ...IRC 3 Programming Manual P N 250060 Revised 14JUL97 firealarmresources com...
Страница 44: ...1 38 Programming Manual firealarmresources com...
Страница 100: ...2 56 Programming Manual Typical Action Response firealarmresources com...
Страница 142: ...3 30 Programming Manual firealarmresources com...
Страница 144: ...firealarmresources com...
Страница 146: ...firealarmresources com...
Страница 148: ...firealarmresources com...
Страница 150: ...firealarmresources com...
Страница 152: ...firealarmresources com...
Страница 154: ...firealarmresources com...
Страница 156: ...firealarmresources com...
Страница 158: ...firealarmresources com...
Страница 160: ...firealarmresources com...
Страница 162: ...firealarmresources com...
Страница 164: ...firealarmresources com...
Страница 166: ...firealarmresources com...
Страница 168: ...firealarmresources com...
Страница 170: ...firealarmresources com...
Страница 172: ...firealarmresources com...
Страница 174: ...firealarmresources com...
Страница 176: ...firealarmresources com...
Страница 178: ...firealarmresources com...
Страница 180: ...firealarmresources com...
Страница 182: ...firealarmresources com...
Страница 184: ...firealarmresources com...
Страница 186: ...firealarmresources com...
Страница 188: ...firealarmresources com...
Страница 190: ...firealarmresources com...
Страница 192: ...firealarmresources com...
Страница 194: ...firealarmresources com...
Страница 196: ...firealarmresources com...
Страница 198: ...firealarmresources com...
Страница 200: ...firealarmresources com...
Страница 202: ...firealarmresources com...
Страница 204: ...firealarmresources com...
Страница 228: ...firealarmresources com...
Страница 232: ...firealarmresources com...
Страница 234: ...firealarmresources com...
Страница 236: ...firealarmresources com...
Страница 238: ...firealarmresources com...
Страница 240: ...firealarmresources com...
Страница 242: ...firealarmresources com...
Страница 244: ...firealarmresources com...
Страница 245: ...IRC 3 Operations Manual P N 270180 Rev 3 5 14JUL97 firealarmresources com...
Страница 250: ...iv Operations Manual firealarmresources com...
Страница 283: ...firealarmresources com...