5.3.1 Dispenser wiring
Formula 1 requires 120 VAC to operate. The dispenser comes with a
pre-installed 9’ electrical cord and is ready to plug in. If a condition exists
where the cord cannot be used (i.e., distances greater than 9’) the
following procedure should be used.
NOTE:
It is not recommended to use power from a laundry
machine to operate the dispenser.
NOTE:
This dispenser must remain powered constantly, do
not use outlets that can be shut off manually (GFI
outlets are OK).
NOTE:
If a condition exists where the cord cannot be used
(i.e., distances greater than 9’) a minimum of 14-ga.
wire enclosed in conduit or Seal-Tite is required. All
local codes must be followed.
1. Remove the existing BROWN and BLUE wires off of the terminal
posts on the back of the ON/OFF circuit breaker (BROWN is hot,
BLUE is neutral).
2. Remove the GREEN wire with the YELLOW tracer from the ground
lug (GREEN is ground).
3. Remove the 9’ power cord from the dispenser electrical enclosure.
4. Field-wire a new HOT, NEUTRAL and GROUNDWIRES within the
electrical enclosure. These MUST BE brought into the electrical
enclosure in conduit or Seal-Tite.
5. Attach the HOT and NEUTRAL wires to the terminal posts on the
back of the ON/OFF circuit breaker. Use the same polarity as the cord
installation. Brown is hot, blue is neutral.
6. Attach the GROUND wire to the grounding lug located on the front of
the electrical enclosure.