EDR-5000
IM02602007E
Name
Description
Bkr.Interl CLOSE1-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE2-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE3-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl OPEN1-I
State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN2-I
State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN3-I
State of the module input: Interlocking of the OPEN command
Bkr.SC CLOSE-I
State of the module input: Switching CLOSE Command, e.g. the state of the Logics or the state of the digital
input
Bkr.SC OPEN-I
State of the module input: Switching OPEN Command, e.g. the state of the Logics or the state of the digital
input
Bkr.Operations Alarm
Signal: Service Alarm, too many Operations
Bkr.Isum Intr trip: IA
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IA
Bkr.Isum Intr trip: IB
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IB
Bkr.Isum Intr trip: IC
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IC
Bkr.Isum Intr trip
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded in at least one
phase.
Bkr.Res TripCmdCr
Signal: Resetting of the Counter: total number of trip commands
Bkr.Res Isum trip
Signal: Reset summation of the tripping currents
Bkr.WearLevel Alarm
Signal: Breaker Wear curve Alarm
Bkr.WearLevel Lockout
Signal: Breaker Wear Curve Lockout Level
Bkr.Res Bwear Curve
Signal: Reset of the Breaker Wear maintenance curve.
Bkr.Isum Intr ph Alm
Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
Bkr.Res Isum Intr ph Alm
Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has been exceeded".
50P[1].Active
Signal: Active
50P[1].ExBlo
Signal: External Blocking
50P[1].Rvs Blo
Signal: Reverse Blocking
50P[1].Blo TripCmd
Signal: Trip Command blocked
50P[1].ExBlo TripCmd
Signal: External Blocking of the Trip Command
50P[1].Pickup IA
Signal: Pickup IA
50P[1].Pickup IB
Signal: Pickup IB
50P[1].Pickup IC
Signal: Pickup IC
50P[1].Pickup
Signal: Pickup
50P[1].Trip Phase A
Signal: General Trip Phase A
50P[1].Trip Phase B
Signal: General Trip Phase B
50P[1].Trip Phase C
Signal: General Trip Phase C
50P[1].Trip
Signal: Trip
50P[1].TripCmd
Signal: Trip Command
50P[1].DefaultSet
Signal: Default Parameter Set