EDR-5000
IM02602007E
Device Planning Parameters of the IRIG-B00X
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Direct Commands of the IRIG-B00X
Parameter
Description
Setting range
Default
Menu path
Res IRIG-B Cr
Resetting of the Diagnosis Counters: IRIG-B
Inactive,
Active
Inactive
[Operation
/Reset]
Global Protection Parameters of the IRIG-B00X
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Device Para
/Time
/TimeSync
/IRIG-B]
IRIG-B00X
Determination of the Type: IRIG-B00X. IRIG-B types
differ in types of included “Coded Expressions” (year,
control-functions, straight-binary-seconds).
IRIGB-000,
IRIGB-001,
IRIGB-002,
IRIGB-003,
IRIGB-004,
IRIGB-005,
IRIGB-006,
IRIGB-007
IRIGB-000
[Device Para
/Time
/TimeSync
/IRIG-B]