EDR-5000
IM02602007E
Direct Commands of the Switchgear/Breaker
Parameter
Description
Setting range
Default
Menu path
Res Bwear Sl
Breaker
Resetting the slow breaker alarm
Inactive,
Active
Inactive
[Operation
/Reset]
Ack TripCmd
Acknowledge Trip Command
Inactive,
Active
Inactive
[Operation
/Reset]
Global Protection Parameters of the Switchgear/Breaker
Parameter
Description
Setting range
Default
Menu path
CinBkr-52a
The breaker is in CLOSE-position if the state of the
assigned signal is true (52a).
1..n, Dig Inputs
DI-8P X1.DI 5
[Control
/Bkr
/Pos Indicatrs
Wirng]
CinBkr-52b
The breaker is in OPEN-position if the state of the
assigned signal is true (52b).
1..n, Dig Inputs
DI-8P X1.DI 6
[Control
/Bkr
/Pos Indicatrs
Wirng]
Ready
Breaker is ready for operation if the state of the assigned
signal is true. This digital input can be used by some
protective elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a trigger signal.
1..n, Dig Inputs
-.-
[Control
/Bkr
/Pos Indicatrs
Wirng]
Interl CLOSE1
Interlocking of the CLOSE command
1..n, Assignment
List
Wired Inputs.Bkr
Trouble-I
[Control
/Bkr
/Interlockings]
Interl CLOSE2
Interlocking of the CLOSE command
1..n, Assignment
List
-.-
[Control
/Bkr
/Interlockings]
Interl CLOSE3
Interlocking of the CLOSE command
1..n, Assignment
List
-.-
[Control
/Bkr
/Interlockings]