Zone Interlocking Wiring
The
ZI Outputs are for use with connection to electronic inputs only.
The zone interlocking connection between relays is done by means of a twisted shielded cable. Downstream zone
interlock outputs may be paralleled from up to ten devices (FP-5000 or DT-3000 or a combination of both) for
connection to upstream zone interlocked relays.