Parameter Set Parameters of the Reactive Power Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
LOP Blo
Measuring Circuit Supervision Voltage
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
CTS Blo
Measuring Circuit Supervision Current
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]