Parameter
Description
Setting range
Default
Menu path
Decoupling3
Decoupling signal that triggers the reclosure.
ReclosureTrigger
-.-
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling4
Decoupling signal that triggers the reclosure.
ReclosureTrigger
-.-
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling5
Decoupling signal that triggers the reclosure.
ReclosureTrigger
-.-
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
Decoupling6
Decoupling signal that triggers the reclosure.
ReclosureTrigger
-.-
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/ReclosureTrigger]
VLL> Release
Minimum voltage (line-to-line) for reclosure (Restoration
Voltage)
Only available if: Reclosure Release Cond = V Internal
Release
0.70 - 1.00Vn
0.95Vn
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
f<
Lower frequency limit for the reclosure (Restoration
Voltage)
40.00 - 69.90Hz
47.5Hz
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]
f>
Upper freqeuncy limit for the reclosure
40.00 - 69.90Hz
50.05Hz
[Protection Para
/<1..4>
/Q->&V<
/Reclosure
/Release]